Universal Digital Modems Ethernet
UniMod ETHERNET |
 |

|
|
|

|
| Brief description |
| |
|
The universal modem UniMod Ethernet ( for LAN / Local
Area Networks) is supposed for remote inquiry of measurement data of any
kind, especially however for telecounting applications.
For the UniMod Ethernet communication modules produced by internationally
renowned companies are used. These companies update their software packages
regularly and add or change features. The software releases are
continuously checked by the development department, but no responsibility
for this software releases can be take over except of warranty granted by
the module producer.
The modem has a built-in, low-loss switched power supply, which enables it
to operate on a wide-range AC or DC supply voltage.
The modem can be programmed with the Hayes AT command set.
Housing outline drawing
|

|
| Interfaces |
| |
|
The interface for connecting the target device can be
specified by plugging the appropriate interface module. The following
module types are available now:
- CS (20 mA current loop) interface module, active (supplies current)
or passive
- RS232 interface module (uses signals RxD, TxD, CTS, RTS, GND)
- RS485 interface module
- M-Bus interface module, active (can supply 10 devices max.) or
passive
|

|
| Technical Data |
| |
| Housing: |
Wall-mounted housing |
| Degree of protection: |
IP52 (IEC) |
| Abmessungen: |
W = 105 mm,
H = 179 mm,
D = 72 mm |
| Protection class: |
1 |
| Supply voltage: |
AC: 80V~ bis 270V~
DC: 60V= bis 375V= |
| Power consumption: |
About 4 VA
(depends upon supply voltage, kind of interface module and
operating status of transmission unit)
|
| Interfaces: |
Plug-in modules; available are:
- RS232 (supports signals RxD, TxD, RTS, CTS, GND, DTR, DCD/DSR)
- CS (20 mA current loop) active or passive
- RS485
- M-Bus active (can supply 10 devices max.) or passive |
| Display: |
LED’s for signals: operation, Rst, Hook, TxD,
RxD. |
| Transmission rate remote modem to
UniMod: |
10 Mbits/s (IEEE802.3) |
| Transmission rate UniMod to connected
device: |
300 to 19200 Baud |
| Ethernet connection: |
10 Base-T |
| Protocols: |
ARP, ICMP, TCP/IP, UDP/IP |
| Software-Interface: |
Hayes Standard-AT |
| Extent of delivery: |
- UniMod Ethernet including interface module as
ordered
- RJ45 connector
- Operation manual |
| Reset circuit: |
optional: every 3, 6, 12 or 24 hours |
| Accessories: |
- Adapter for parametering (#9177)
- Additional interface modules
- Parameterization software UniModSet / MetcomTSet
|
| Download as PDF File: |
UniMod Ethernet Flyer (Filesize
248K)
UniMod Ethernet Operation Manual (Filesize
1.0M)
|
|
| |

|
| UniMod ETHERNET housing outline drawing |
| |
 |
| |
 |
| |
 |
| |
|
|
|